Calculateur de calibre de disjoncteur

Estimez un courant nominal standard à partir du courant de charge ou de P, V, phase et facteur de puissance. Charge continue 125 % optionnelle. Pas un substitut au code.

Courant connu. Vide pour estimer avec puissance et tension.

Ou estimer depuis la puissance

Puissance active (watts).

Monophasé : tension selon votre schéma.

1 pour résistif ; moteurs souvent 0,8–0,95.

Table of Contents

Outil de planification

Breakers (or fuses) protect conductors and equipment by opening when current is too high. Their ampere rating must be chosen using applicable codes, manufacturer listings, conductor ampacity, and site conditions.

This calculator picks the smallest common standard rating that is still at least your design current — the current you must not exceed on the protected circuit under your assumptions.

You may enter load current directly (from a nameplate, load calc, or engineer), or estimate it from real power, voltage, single- vs three-phase, and power factor.

Real projects need temperature correction, terminal limits, feeder vs branch rules, harmonic loads, motor inrush, GFCI/AFCI requirements, and utility or AHJ rules. Use this for quick estimates and education only.

Formulas used here

Operating current from power

Single-phase: I = P ÷ (V × PF). Three-phase: I = P ÷ (√3 × V_L-L × PF).

P is real power in watts, V is the voltage defined above for the selected phase mode, PF is power factor.

Continuous loads

If “continuous” is enabled: I_design = I_operating × 1.25, then choose the next standard breaker ≥ I_design.
Breakers are then matched to conductor ampacity and code requirements in the field.

Quick Reference (illustrative)

LoadVφCont.Breaker (A)Note
1,920 W2401No10I = 8 A → often 10 A or 15 A minimum branch per local rules
12,000 W2401Yes70I ≈ 50 A, ×1.25 = 62.5 A → next standard 70 A
15 kW4003No32I ≈ 21.7 A at PF 1 → 25 or 32 A commonly stocked
30 ANo30Direct amp entry; next size ≥ 30 A

Real-World Examples

240 V single-phase heater

6,000 W, PF 1 → I = 6,000 ÷ 240 = 25 A. Non-continuous → next standard ≥25 A is often 30 A; verify conductor size and code minimums.

Small motor branch

Motors need Article 430 / local motor rules; this tool only converts watts to current. Use nameplate FLA and code tables for OCPD and conductor sizing.

Three-phase workshop

10 kW, 400 V L-L, PF 0.9 → I = 10,000 ÷ (√3 × 400 × 0.9) ≈ 16.0 A → common breaker 20 A or 25 A depending on supply and derating.

Continuous lighting load

If a load runs 3+ hours and is classified continuous, enable 125% so continuous current does not exceed 80% of the breaker rating in typical NEC-style planning.

FAQ

Why might the next size up still be wrong in practice?

Conductor ampacity, ambient temperature, number of conductors in a raceway, terminal temperature limits, and listing instructions can require a larger wire or a different OCPD rating than this estimate suggests.

120 V vs 240 V for single-phase — which do I enter?

Use the voltage that matches how you computed or measured load current. A 240 V water heater uses 240 in this field; a 120 V branch uses 120. Three-phase always uses line-to-line voltage here.

I entered both amps and watts. Which wins?

If load current (A) is filled with a valid positive number, that value is used and the power fields are ignored until you clear amps.

Does this pick GFCI or AFCI breakers?

No. It only suggests a common thermal-magnetic amp rating for planning. Device class (GFCI/AFCI/CAFCI), curves, and interrupting rating are separate selections.

What about fuses instead of breakers?

Standard fuse amp ratings are often similar, but fuse curves and code rules differ. Treat the suggested amperes as an order-of-magnitude check, not a fuse part number.

Related tools on Tooladex

Convert power and time with our electrical calculators (watts, amps, volts, kWh) to feed better numbers into this breaker planner.

Share this tool

Share a direct link or embed this tool on your site. Keep the Tooladex attribution link to support the project.